2 Parameters
2.2 List of parameters
SINAMICS G130/G150
232 List Manual (LH2), 07/2016, A5E03263479A
For p0601 = 10:
Not permitted for p0600 = 0, 10, 11.
Associated parameters: p4600 ... p4603 (can be switched via EDS)
For r0458.8 = 1, a temperature evaluation is supported through several temperature channels.
Examples:
When evaluating using SME120 or SME125, 4 temperature channels are available (parameterized using p4600,
p4601, p4602, p4603).
When evaluating using CU310 and CUA32, 2 temperature channels are available (encoder interface:
parameterization via p4600, terminal block: parameterization via p4601).
For p0601 = 11:
Not permitted for p0600 = 0, 10, 11.
Associated parameters: p4610 ... p4613 (can be switched via MDS)
Description: Sets the sensor type for the temperature measurement at input X21 (booksize) or X41 (chassis).
The measured value is displayed in r0035.
Value: 0: No sensor
1: PTC alarm & timer
2: KTY84
4: Bimetallic NC contact alarm & timer
6: PT1000
Dependency: Refer to: r0035
Note: The measured value display depends on the selected sensor type.
For p0601 = 0:
--> r0035 = -200 °C
For p0601 = 1:
Tripping resistance = 1650 Ohm (lower resistance --> r0035 = -50 °C, higher resistance --> r0035 = 250 °C).
For p0601 = 2, 6:
Displays the temperature in °C.
For p0601 = 4:
r0035 = -50 °C
--> The tripping resistance is less than 100 Ohm (bimetallic NC contact is closed or has a short-circuit).
r0035 = 250 °C
--> The tripping resistance is greater than 100 Ohm (bimetallic NC contact is open, not connected or has a wire
breakage).
When using the following components, a value of 4 is set as the factory setting and can no longer be changed:
- Basic Line Module (BLM) with internal Braking Module.
- Active Line Module (ALM) with line filter Active Interface Module (AIM, p0220[0] = 41 ... 45).
In these cases, in addition to the temperature display, the temperature is also monitored.
Description: Sets the power unit number to which the temperature sensor is connected. The value corresponds to the Power unit
Data Set number (PDS) of the power unit. The number of power unit data sets is defined in p0120.
p0601 Temperature sensor, sensor type / Temp_sens type
B_INF Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 6 0
p0602 Par_connection power unit number, temperature sensor / PU_no temp_sensor
VECTOR_G (Parallel) Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting