A35907 (F, N) TM: Hardware initialization error
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, TM120, TM150, TM31, VECTOR_G
Component: Terminal Module (TM) Propagation: BICO
Reaction: NONE
Acknowledge: NONE
Cause: The Terminal Module was not successfully initialized.
Alarm value (r2124, interpret hexadecimal):
01: TM17 or TM41 - incorrect configuration request.
02: TM17 or TM41 - programming not successful.
04: TM17 or TM41 - invalid time stamp
Remedy: Carry out a POWER ON.
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE
A35910 (F, N) TM: Module overtemperature
Message value: -
Message class: Overtemperature of the electronic components (6)
Drive object: B_INF, TM120, TM150, TM31, VECTOR_G
Component: Terminal Module (TM) Propagation: BICO
Reaction: NONE
Acknowledge: NONE
Cause: The temperature in the module has exceeded the highest permissible limit.
Remedy: - reduce the ambient temperature.
- replace the Terminal Module.
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE
A35911 (F, N) TM: Clock synchronous operation sign-of-life missing
Message value: -
Message class: Communication error to the higher-level control system (9)
Drive object: B_INF, TM120, TM150, TM31, VECTOR_G
Component: None Propagation: BICO
Reaction: NONE
Acknowledge: NONE
Cause: The maximum permissible number of errors in the master sign-of-life (clock synchronous operation) has been
exceeded in cyclic operation.
When the alarm is output, the module outputs are reset up to the next synchronization.
Remedy: - check the physical bus configuration (terminating resistor, shielding, etc.).
- check the interconnection of the master sign-of-life (r4201 via p0915).
- check whether the master correctly sends the sign-of-life (e.g. set up a trace with r4201.12 ... r4201.15 and trigger
signal r4301.9).
- check the bus and master for utilization level (e.g. bus cycle time Tdp was set too short).
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE