Description: Display and connector output for the measured actual value of the DC link voltage.
Dependency: Refer to: r0026
Notice: For SINAMICS S120 AC Drive (AC/AC) the following applies:
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM340) a valid measured value is not
supplied. In this case, when an external 24V power supply is connected, a value of approx. 24 V is displayed.
Note: The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
Description: Display and connector output for the measured actual value of the DC link voltage.
Dependency: Refer to: r0026
Note: The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
Description: Displays the maximum output voltage.
Dependency: The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note: As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link
voltage.
Description: Display and connector output for the actual output voltage of the power unit (Motor Module).
Dependency: Refer to: r0025
Note: The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0070 CO: Actual DC link voltage / Vdc act val
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6723, 6724,
6730, 6731, 6799
P-Group: Displays, signals Unit group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r0070 CO: Actual DC link voltage / Vdc act val
B_INF Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8750, 8850,
8910, 8940, 8950, 8964
P-Group: Displays, signals Unit group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r0071 Maximum output voltage / U_output max
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6301, 6640,
6700, 6722, 6723, 6724, 6725,
6727
P-Group: Displays, signals Unit group: 5_1 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0072 CO: Output voltage / U_output
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 5700, 5730,
6730, 6731, 6799
P-Group: Displays, signals Unit group: 5_1 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]