Siemens G130 - p3682 Braking Module internal DC link fast discharge delay time; BM int DC dischg t; p3683 Braking Module internal activation threshold brake chopper; BM int act thresh; r3685 BO: Digital Braking Module: Pre-alarm I2 t shutdown; Dig BM A I2 t shutd; r3686 BO: Digital Braking Module fault; Dig BM fault

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
615
2 Parameters
2.2 List of parameters
Description: Sets the delay time for switching in the DC link fast discharge for an internal Braking Module.
Dependency: Refer to: p3681
Notice: The parameter is only effective for Basic Line Modules with the internal Braking Module (this is valid for Basic Line
Modules with a power rating of less than 100 kW).
Description: Sets the activation threshold for the braking chopper.
Note: The activation threshold is only effective if the "Device supply voltage reduced" function (p0212.0 = 1) has been
activated!
Description: The binector output uses a 1 signal to indicate that 80 % of the highest permissible I2t value has been reached in the
Braking Module.
Dependency: Refer to: A06905
Description: The binector output uses a 1 signal to indicate an overcurrent fault or an I2t shutdown in the Braking Module.
Dependency: Refer to: F06906
p3682 Braking Module internal DC link fast discharge delay time / BM int DC dischg t
B_INF Can be changed: C1(3), T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
500 [ms] 4294967295 [ms] 1000 [ms]
p3683 Braking Module internal activation threshold brake chopper / BM int act thresh
B_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
110.00 [V] 780.00 [V] 760.00 [V]
r3685 BO: Digital Braking Module: Pre-alarm I2t shutdown / Dig BM A I2t shutd
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r3686 BO: Digital Braking Module fault / Dig BM fault
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -