2 Parameters
2.2 List of parameters
Description: Sets the delay time for switching in the DC link fast discharge for an internal Braking Module.
Dependency: Refer to: p3681
Notice: The parameter is only effective for Basic Line Modules with the internal Braking Module (this is valid for Basic Line
Modules with a power rating of less than 100 kW).
Description: Sets the activation threshold for the braking chopper.
Note: The activation threshold is only effective if the "Device supply voltage reduced" function (p0212.0 = 1) has been
activated!
Description: The binector output uses a 1 signal to indicate that 80 % of the highest permissible I2t value has been reached in the
Braking Module.
Dependency: Refer to: A06905
Description: The binector output uses a 1 signal to indicate an overcurrent fault or an I2t shutdown in the Braking Module.
Dependency: Refer to: F06906
p3682 Braking Module internal DC link fast discharge delay time / BM int DC dischg t
B_INF Can be changed: C1(3), T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
500 [ms] 4294967295 [ms] 1000 [ms]
p3683 Braking Module internal activation threshold brake chopper / BM int act thresh
B_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
110.00 [V] 780.00 [V] 760.00 [V]
r3685 BO: Digital Braking Module: Pre-alarm I2t shutdown / Dig BM A I2t shutd
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r3686 BO: Digital Braking Module fault / Dig BM fault
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -