Siemens G130 - p0869 Sequence control configuration; Seq_ctrl config; r0873 CO;BO: Infeed total operation; INF total oper

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
284 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the configuration for the sequence control.
Dependency: Refer to: p0867
Note: For bit 00:
After withdrawing the OFF1 enable (signal source of p0840), the main contactor is opened after the main contactor
holding time has elapsed.
For p0869.0 = 1, after withdrawing STO, the switching-on inhibited must be acknowledged via the signal source of
p0840 = 0 (OFF1) – and before the main contactor holding time expires (p0867), should go back to 1, otherwise the
main contactor will open.
Description: Sets the configuration for the sequence control.
Notice: For chassis units, the following applies:
Setting p0869.1 = 1 is not permissible, if, using p0860 the internal circuit breaker is monitored (this is not controlled
with r0863.1).
Note: For bit 01:
For p0869.1 = 1, before starting to charge the DC link (r0899.8 = 1), the system waits for a feedback signal from the
external main contactor (p0860 = 1 signal). The main contactor must be controlled using r0863.1.
Waiting for the contactor feedback signal is especially necessary if the external main contactor has long switching
times, which would lead to the precharging time being exceeded (F06000, F30027).
Description: Displays the operational readiness of the infeeds when using Smart Line Module (SLM) and Basic Line Module
(BLM) together (mixed operation).
In order that signal BO: r0873 is available at one of the infeeds, then BI: p0874 of the one infeed must be
interconnected to BO: r0863.0 of the other infeed.
Dependency: Refer to: r0863, p0874
Note: Mixed operation is not possible with the Active Line Module (ALM)!
p0869 Sequence control configuration / Seq_ctrl config
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Keep main contactor closed for STO Yes No -
p0869 Sequence control configuration / Seq_ctrl config
B_INF Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 8732, 8832,
8932
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Wait for the feedback signal from the
external main contactor
Yes No -
r0873 CO/BO: Infeed total operation / INF total oper
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8732, 8832
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -