EasyManua.ls Logo

Siemens G130 - r0193 Power unit firmware properties 2; PU FW property 2; r0194[0...n] VSM properties; VSM properties; r0196[0...255] Topology component status; Top comp stat

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
107
2 Parameters
2.2 List of parameters
Description: Displays the properties supported by the power unit firmware.
Dependency: Refer to: r0192
Description: Displays the properties supported by the Voltage Sensing Module (VSM).
Description: Displays the status of the components.
r0196[0]: group status of all components
r0196[1]: Status of component with component number 1
...
r0196[255]: Status of component with component number 255
r0193 Power unit firmware properties 2 / PU FW property 2
VECTOR_G, B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 Component trace Yes No -
06 PT1000 temperature sensor evaluation Yes No -
08 Reduced undervoltage threshold during
precharging
Yes No -
09 Switchover to 1-phase line voltage Yes No -
r0194[0...n] VSM properties / VSM properties
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: p0150 Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Reserved Yes No -
r0196[0...255] Topology component status / Top comp stat
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Component status bit 0 High Low -
01 Component status bit 1 High Low -
02 Component status bit 2 High Low -
03 Component status bit 3 High Low -
04 Component state Active Inactive/parking -
06 Topology problem active Yes No -
07 Part of the target topology Yes No only act topo -
08 Alarm present Yes No -
09 Safety message present Yes No -
10 Fault present Yes No -
11 Alarm class bit 0 High Low -
12 Alarm class bit 1 High Low -
13 Maintenance required Yes No -
14 Maintenance urgently required Yes No -
15 Fault gone/can be acknowledged Yes No -

Table of Contents