SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
107
2 Parameters
2.2 List of parameters
Description: Displays the properties supported by the power unit firmware.
Dependency: Refer to: r0192
Description: Displays the properties supported by the Voltage Sensing Module (VSM).
Description: Displays the status of the components.
r0196[0]: group status of all components
r0196[1]: Status of component with component number 1
...
r0196[255]: Status of component with component number 255
r0193 Power unit firmware properties 2 / PU FW property 2
VECTOR_G, B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 Component trace Yes No -
06 PT1000 temperature sensor evaluation Yes No -
08 Reduced undervoltage threshold during
precharging
Yes No -
09 Switchover to 1-phase line voltage Yes No -
r0194[0...n] VSM properties / VSM properties
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: p0150 Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Reserved Yes No -
r0196[0...255] Topology component status / Top comp stat
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Component status bit 0 High Low -
01 Component status bit 1 High Low -
02 Component status bit 2 High Low -
03 Component status bit 3 High Low -
04 Component state Active Inactive/parking -
06 Topology problem active Yes No -
07 Part of the target topology Yes No only act topo -
08 Alarm present Yes No -
09 Safety message present Yes No -
10 Fault present Yes No -
11 Alarm class bit 0 High Low -
12 Alarm class bit 1 High Low -
13 Maintenance required Yes No -
14 Maintenance urgently required Yes No -
15 Fault gone/can be acknowledged Yes No -