Siemens G130 - p3242[0...n] I2 t maximum duration; I2 t max_dur; p3243[0...n] I2 t alarm thresh; I2 t alarm thresh; r3244 CO: Actual I2 t integrator value; Act I2 t integ_val

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
602 List Manual (LH2), 07/2016, A5E03263479A
Dependency: Refer to: p3240, p3242, p3243, r3244
Refer to: A07823, F07824
Description: Sets the maximum duration for 100 % overload (corresponding to p3241 + 100 %) of the freely parameterizable I2t
monitoring.
Setting example:
Operation should be possible at 150 % of the input quantity for a duration of 3 s for a permissible continuous value
p3241 = 110 %.
As a consequence, the following settings value is obtained:
p3242 = ((150 x 150 - 110 x 110) / ((100 + 110) x (100 + 110) - 110 x 110) x 3 s = 0.975 s
Dependency: Refer to: p3240, p3241, p3243, r3244
Refer to: A07823, F07824
Notice: For p3242 = 0, the freely parameterizable I2t monitoring is deactivated.
Note: After this time expires for 100 % overload, fault F07824 is output and status bit r2199.14 is set.
For lower overload conditions, the permissible duration extends corresponding to the specified setting example.
Description: Sets the alarm threshold for the I2t integrator value (r3244) scaled to 100 %.
When the alarm threshold is reached, alarm A07823 is output and status bit r2199.13 is set.
Dependency: Refer to: p3240, p3241, p3242, r3244
Refer to: A07823
Description: Display and connector output for the actual integrator value of the freely parameterizable I2t monitoring.
The value is scaled, so that the maximum permissible overload is reached at 100 %.
Dependency: Refer to: p3240, p3241, p3242, p3243
p3242[0...n] I2t maximum duration / I2t max_dur
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8022
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 3600.00 [s] 0.00 [s]
p3243[0...n] I2t alarm thresh / I2t alarm thresh
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8022
P-Group: - Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 99.90 [%] 50.00 [%]
r3244 CO: Actual I2t integrator value / Act I2t integ_val
VECTOR_G (Ext msg) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8022
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]