SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
857
2 Parameters
2.2 List of parameters
Description: Display for the maximum interconnected PZD in the receive/send direction
Index 0: receive (r8850, r8860)
Index 1: send (p8851, p8861)
Description: Assignment of a PZD to a telegram word from a SINAMICS Link receive telegram.
For p8839[0] = 2 (COMM BOARD via interface 1), the following applies:
- PZD p2050[index] is assigned by means of p8870[index], p8872[index].
For p8839[1] = 2 (COMM BOARD via interface 2), the following applies:
- using p8870[index], p8872[index], the PZD is assigned r8850[Index].
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency: Refer to: p8872
Note: Value range:
0: Not used
1 ... 32: telegram word
A pair of values p8870[index], p8872[index] may only be used once in single a device.
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
r8867[0...1] IF2 PZD maximum interconnected / IF2 PZDmaxIntercon
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP,
VECTOR_G, B_INF,
TM31, TM120, TM150,
TB30, ENC
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p8870[0...15] SINAMICS Link PZD receive word / PZD recv word
CU_G130_PN (PN
CBE20),
CU_G150_PN (PN
CBE20),
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20), B_INF (PN
CBE20), TM31 (PN
CBE20), TM120 (PN
CBE20), TM150 (PN
CBE20), TB30 (PN
CBE20), ENC (PN
CBE20)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2198, 2199
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 32 0