SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
803
2 Parameters
2.2 List of parameters
Description: Display and connector output for the signal interconnected via connector input p8505.
Dependency: Refer to: p8505
Description: Setting for saving the actual configuration of the Advanced Operator Panel (AOP).
Description: Sets the unit for displaying and entering speeds.
Value: 1: Hz
2: rpm
Description: Displays the macro file saved in the appropriate directory on the memory card/device memory.
Dependency: Refer to: p0015
Note: For a value = 9999999, the following applies: The read operation is still running.
r8515 CO: Output signal wordwise 3 / Outp_sig word 3
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2195
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p8550 AOP LOCAL/REMOTE / AOP LOCAL/REMOTE
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 1001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 LOCAL save Yes No -
01 Start in LOCAL Yes No -
02 Change in oper Yes No -
03 OFF acts like OFF1 Yes No -
04 OFF acts like OFF2 Yes No -
05 OFF acts like OFF3 Yes No -
06 Reserved Yes No -
07 CW/CCW active Yes No -
08 Jog active Yes No -
09 Save speed setpoint Yes No -
14 Inhibit operation Yes No -
15 Inhibit parameterization Yes No -
p8552 IOP speed unit / IOP speed unit
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 2 2
r8570[0...39] Macro drive object / Macro DO
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP,
VECTOR_G, B_INF,
TM31, TM120, TM150
Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -