SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
647
2 Parameters
2.2 List of parameters
Description: Setting to invert the signals at the digital outputs of Terminal Module 31 (TM31).
Note: DO: Digital Output
DI/DO: Bidirectional Digital Input/Output
Description: Setting to invert the signals at the digital outputs of the Terminal Board 30 (TB30).
Note: DO: Digital Output
Description: Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The type of analog input AI x (voltage or current input) is set using p4056.
Refer to: r4056, p4056
Note: AI: Analog Input
p4048 TM31 invert digital outputs / TM31 DO inv
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9556, 9560,
9562
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X542.1 - 3) Inverted Not inverted -
01 DO 1 (X542.4 - 6) Inverted Not inverted -
08 DI/DO 8 (X541.2) Inverted Not inverted -
09 DI/DO 9 (X541.3) Inverted Not inverted -
10 DI/DO 10 (X541.4) Inverted Not inverted -
11 DI/DO 11 (X541.5) Inverted Not inverted -
p4048 TB30 invert digital outputs / TB30 DO inv
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9102
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X481.5) Inverted Not inverted -
01 DO 1 (X481.6) Inverted Not inverted -
02 DO 2 (X481.7) Inverted Not inverted -
03 DO 3 (X481.8) Inverted Not inverted -
r4052[0...1] CO: TM31 analog inputs current input voltage/current / TM31 AI U/I_inp
TM31 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -