2 Parameters
2.2 List of parameters
SINAMICS G130/G150
722 List Manual (LH2), 07/2016, A5E03263479A
Description: The function generator is started with p4800 = 1.
The signal is only generated for a 1 signal of binector input p4819.
Value: 0: Stop function generator
1: Start function generator
2: Check function generator parameterization
3: Start function generator without enable signals
Dependency: Refer to: p4819
Description: Displays the actual status of the function generator.
Value: 0: Inactive
1: Generate accelerating ramp to offset
2: Generate parameterized signal shape
3: Generate braking ramp
4: Function generator stopped due to missing enable signals
5: Function generator waits for BI: p4819
6: Function generator parameterization has been checked
Dependency: Refer to: p4800, p4819
Description: Displays the status of the function generator.
0 signal: Function generator inactive
1 signal: Function generator running
p4800 Function generator control / FG control
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0 3 0
r4805 Function generator status / FG status
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0 6 -
r4806.0 BO: Function generator status signal / FG status signal
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -