2 Parameters
2.2 List of parameters
SINAMICS G130/G150
136 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the stall current for synchronous motors (p0300 = 2xx), as well as for synchronous reluctance motors (p0300 =
6xx).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The parameter is used for the I2t monitoring of the motor (refer to p0611).
This parameter is not used for induction motors (p0300 = 1xx).
For synchronous reluctance motors, the current corresponds to a winding temperature increase of 105 K at a speed
of 20 % of the rated speed.
Description: Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The magnetization current p0320 for induction motors (not for catalog motors) is reset when quick commissioning is
exited with p3900 > 0.
VECTOR:
If, for induction motors, the magnetizing current p0320 is changed outside the commissioning phase (p0010 > 0),
then the magnetizing inductance p0360 is changed so that the EMF r0337 remains constant.
Description: Sets the maximum motor speed.
Dependency: Refer to: p1082
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0322 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010 =
3).
Note: The parameter has no significance for a value of p0322 = 0.
p0318[0...n] Motor stall current / Mot I_standstill
VECTOR_G Can be changed: C2(3) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0320[0...n] Motor rated magnetizing current/short-circuit current / Mot I_mag_rated
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 5722
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 [Arms] 5000.000 [Arms] 0.000 [Arms]
p0322[0...n] Maximum motor speed / Mot n_max
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [rpm] 210000.0 [rpm] 0.0 [rpm]