SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
251
2 Parameters
2.2 List of parameters
Description: Displays the measuring time for a falling edge at the digital input for the "central measuring probe evaluation"
function.
The measuring time is specified as 16-bit value with a resolution of 0.25 µs.
r0687[0]: Measuring time, falling edge measuring probe 1
r0687[1]: Measuring time, falling edge measuring probe 2
r0687[2]: Measuring time, falling edge measuring probe 3
r0687[3]: Measuring time, falling edge measuring probe 4
r0687[4]: Measuring time, falling edge measuring probe 5
r0687[5]: Measuring time, falling edge measuring probe 6
r0687[6]: Measuring time, falling edge measuring probe 7
r0687[7]: Measuring time, falling edge measuring probe 8
Note: The parameter is only active for the evaluation procedure p0684 = 0, 1.
For p0684 = 16, r0687[0...7] = 0 is displayed.
Description: Displays the status word for the function "central measuring probe evaluation".
r0687[0...7] CO: Central measuring probe measuring time falling edge / CenMeas t_meas 1/0
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r0688 CO: Central measuring probe status word display / Cen meas ZSW disp
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Digital input measuring probe 1 High Low -
01 Digital input measuring probe 2 High Low -
02 Digital input measuring probe 3 High Low -
03 Digital input measuring probe 4 High Low -
04 Digital input measuring probe 5 High Low -
05 Digital input measuring probe 6 High Low -
06 Digital input measuring probe 7 High Low -
07 Digital input measuring probe 8 High Low -
08 Sub-sampling measuring probe 1 High Low -
09 Sub-sampling measuring probe 2 High Low -
10 Sub-sampling measuring probe 3 High Low -
11 Sub-sampling measuring probe 4 High Low -
12 Sub-sampling measuring probe 5 High Low -
13 Sub-sampling measuring probe 6 High Low -
14 Sub-sampling measuring probe 7 High Low -
15 Sub-sampling measuring probe 8 High Low -