EasyManua.ls Logo

Siemens G130 - Fig. 3-71 2546 - Control word, faults;alarms

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Function diagrams
3.7 Internal control/status words
SINAMICS G130/G150
1178 List Manual (LH2), 07/2016, A5E03263479A
Fig. 3-71 2546 – Control word, faults/alarms
- 2546 -
Function diagram
87654321
fp_2546_51_eng.vsd
DO: All objects
SINAMICS
30.06.14 V04.08.00
Internal control/status words - Control word, faults/alarms
<1> This parameter refers to the Control Unit and is
used as source to simultaneously acknowledge
all faults on all drive objects.
<2> These parameters refer to the Command Data Sets (CDS) depending on the
individual drive object (DO).
p2103[C]1. Acknowledge
p2102Ackn all faults
p2105[C]3. Acknowledge
Pulse generator
11
12
13
14
15
Reserved
Control word, faults/alarms
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
= Acknowledge fault
Reserved
Reserved
1 = External alarm 1 (A07850)
1 = External alarm 2 (A07851)
1 = External alarm 3 (A07852)
1 = External fault 1 (F07860)
1 = External fault 3 (F07862)
1 = External fault 2 (F07861)
PROFIdrive bit
9
10
8
7
6
5
4
3
2
1
0
Bit No.
To alarm buffer [8065.1]r2138.11
To fault buffer [8060.1]
r2138.13
To fault buffer [8060.1]r2138.14
p2112[C] (1)
p2116[C] (1)
p2117[C] (1)
p2106[C] (1)
p2107[C] (1)
To fault buffer [8060.1]r2138.15
To alarm buffer [8065.1]r2138.12
To alarm buffer [8065.1]r2138.10
To fault buffer [8060.1]r2138.7
p2108[C] (1)
p3111[C] (1)
p3112[C] (0)
T0
p3110 [ms]
<2>
<1>
p2104[C]2. Acknowledge
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
1
1
1
1
1
1
r2138
STW faults/alarms
4000.00 μs

Table of Contents

Related product manuals