SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
117
2 Parameters
2.2 List of parameters
For bit 06:
Precharging via the Motor Module is activated using this bit. To do this, while precharging, the undervoltage threshold
for the pulse enable is reduced.
Precharging via the Motor Module can only be activated for S120 devices for separately excited synchronous
generators where the DC link voltage control has been preselected (technology controller function module).
Description: Sets the power unit configuration.
Dependency: For bit 00:
Reduced supply voltages are only possible on booksize power units.
Bit 0 = 1 can only be set if r0192.22 = 1.
Refer to: r0192, p0210
Caution: For bit 00:
Working with reduced input voltages correspondingly reduces undervoltage detection.
This function may only be used by personnel with expert knowledge!
Note: For bit 00 = 0:
It is not possible to reduce the supply voltage in p0210 to below 180 V.
For bit 00 = 1:
With this setting the supply voltage in p0210 can be reduced to 70 V.
Bit 0 = 1 can only be set for booksize power units with a rated power of up to 40 kW.
The activation of this function is retentively saved in the unit and for incorrect design of the application can result in
loss of warranty!
For bit 02:
Reserved. It is not permissible to set to 1.
For bit 05 = 1:
The status of the inputs/outputs for the power unit contactors is displayed in r0256.
This only applies to chassis power units with 3 AC line connection and line contactors.
The status display is only effective after parameter save and POWER ON.
Description: Sets the type of the filter at the motor side.
Value: 0: No filter
1: Motor reactor
2: dv/dt filter
3: Sine-wave filter Siemens
4: Sine-wave filter third-party
Dependency: The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power unit, motor reactor) = filter inductance
p0212 Power unit configuration / PU config
B_INF Can be changed: C2(2) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Drive unit line supply voltage reduced Yes No -
02 Reserved Yes No -
05 Contactor display inputs/outputs status Yes No 9814
p0230 Drive filter type motor side / Drv filt type mot
VECTOR_G Can be changed: C2(1, 2) Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4 0