3 Function diagrams
3.8 Sequence control
SINAMICS G130/G150
1182 List Manual (LH2), 07/2016, A5E03263479A
Fig. 3-74 2634 – Missing enables, line contactor control, logic operation
- 2634 -
Function diagram
87654321
fp_2634_54_eng.vsd
DO: SERVO, VECTOR
S120/S150/G130/G150
07.09.15 V04.08.00
Sequence control - Missing enable signals, line contactor control, logic operation
+24 V
Control Unit
Line contactor control
T
p0861
Time monitoring
&
F07300
"Line contactor
feedback signal
missing"
[2120]...[2133]
DI
DO
[2130]...[2133]
r0863.1
Line contactor feedback signal
p0860
Energize line contactor
r0863.1
1
To the infeed
&
1
Operating monitoring
ON/OFF monitoring
0
From the line
supply
p0115[3] (2000.00 μs)
<2>
[2610.4]<2>
[8732.4]<3>
[8832.4]<4>
[8932.4]<5>
Line contactor control from sequence control
1
r0046
Missing enable sig
1
[3060.2]
[3060.4]
[3070.2]
[3070.4]
1 = Internal RFG missing
[3060.2]
[3070.2]
0 = Internal quick stop
<1> Only for VECTOR.
<2> For AC/AC devices, diode infeed.
<3> Only for SINAMICS S120/G150.
<4> Only for SINAMICS S120.
<5> Only for SINAMICS S120/S150.
Logic operation
(0)
p2810[1]
(0)
p2810[0]
r2817.0
r2811.0 (0)
p2822[0]
(0)
p2822[1]
(0)
p2822[2]
(0)
p2822[3]
1
1
r2823.1
1
r2823.2
1
r2823.3
r2823.0
r2823
(0)
p2816[0]
(0)
p2816[1]
AND operation
OR operation
NOT operation
Missing enable signals that prevent the drive going into operation
(this situation can be detected at the ZSW sequence control, infeed r0899.2 = 1 [8926] <5>)
Missing enable signals
<1>
1 = OFF2, enable missing1
2
3
5
9
1 = OFF1, enable missing
Meaning
1 = OFF3, enable missing
1 = Enable operation missing
1 = STOP2, enable missing
1 = Infeed, enable missing
Bit No.
0
10
11
12
1 = Ramp-function generator enable missing
1 = Ramp-function generator start missing
1 = Setpoint, enable missing
16
17
18
1 = OFF1, enable, internal missing
1 = OFF2, enable, internal missing
1 = OFF3, enable, internal missing
26 1 = Drive inactive or not operational
19 1 = Pulse enable, internal missing
25 1 = Function bypass active
27 1 = De-magnetization not completed
28 1 = Open brake missing
4 1 = Armature short-circuit/DC braking, enable missing
8 1 = Safety, enable missing
20
21
1 = Internal armature short circuit/DC braking, enable missing
1 = STOP2, enable internal missing
29
30
31
1 = Cooling system ready missing
1 = Jog setpoint active
1 = Speed controller inhibited
[2701.8]
[3020.5]
r0046.0
r0046.1
r0046.2
r0046.3
r0046.9
r0046.10
r0046.11
r0046.12
r0046.8
r0046.16
r0046.17
r0046.18
r0046.19
r0046.20
r0046.25
r0046.26
r0046.27
r0046.28
r0046.29
r0046.30
r0046.31
r0046.21
r0046.4
15 1 = Quick stop, enable missing r0046.15
r0046.12
r0046.5
Fault with
OFF3 reaction