EasyManua.ls Logo

Siemens G130 - Fig. 3-185 8565 - Drive Data Sets (DDS)

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1307
3 Function diagrams
3.21 Data sets
Fig. 3-185 8565 – Drive Data Sets (DDS)
- 8565 -
Function diagram
87654321
fp_8565_54_eng.vsd
DO: SERVO, VECTOR, TM41
S120/S150/G130/G150
03.07.13 V04.08.00
Data sets - Drive Data Sets (DDS)
Not relevant
Drive n
(0)
Select DDS bit 0
p0820[C]
(0)
Select DDS bit 1
p0821[C]
(0)
Select DDS bit 2
p0822[C]
(0)
Select DDS bit 3
p0823[C]
Copy DDS, source
p0819[0] (0)
Drive 2
Drive 1
Copy DDS, target
p0819[1] (1)
Copy DDS, start
p0819[2] (0)
DDS31
DDS number
p0180 (1)
DDS1
DDS0
(0)
Select DDS bit 4
p0824[C]
DDS selected
r0837.0
r0837
r0837.3
DDS effective
r0051.0
r0051
r0051.4
r0837.2
r0837.1
r0051.3
r0051.2
r0051.1
A07530 "Drive data set does not exist"
r0837.4
r0049
r0049[0] Motor data set MDS effective
r0049[1] Encoder 1 encoder data set EDS effective
r0049[2] Encoder 2 encoder data set EDS effective
r0049[3] Encoder 3 encoder data set EDS effective
r0838
r0838[0] Motor data set MDS selected
r0049[1] Encoder 1 encoder data set EDS selected
r0838[2] Encoder 2 encoder data set EDS selected
r0838[3] Encoder 3 encoder data set EDS selected
MDS (Motor Data Set)
EDS (Encoder Data Set)
DDS (Drive Data Set)
p0186[0...n] (MDS number)
p0187[0...n] (enc 1 EDS number)
p0188[0...n] (enc 2 EDS number)
p0189[0...n] (enc 3 EDS number)
<1>
<1> A BICO interconnection to a parameter which is part of a drive data set always
influences the currently effective data set.
<2> Only for SINAMICS S120/S150.
<2>
<2>
<2>
<2>
<2>
<2>

Table of Contents

Related product manuals