2 Parameters
2.2 List of parameters
SINAMICS G130/G150
60 List Manual (LH2), 07/2016, A5E03263479A
Bit 17 = 1 (enable signal missing), if:
- the commissioning mode is selected (p0009 > 0 or p0010 > 0) or there is an OFF2 fault response or the OFF1
signal source (p0840) is changed.
Bit 26 = 1 (enable signal missing), if:
- the infeed is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 29 = 1 (enable signal missing), if:
- the cooling unit ready signal via binector input p0266[1] missing.
Description: Displays the actual status for the motor data identification (stationary measurement) and the speed/velocity controller
optimization (rotating measurement).
Value: 0: No measurement
115: Measurement q leakage inductance (part 2)
120: Speed controller optimization (vibration test)
140: Calculate speed controller setting
150: Measurement moment of inertia
170: Measurement magnetizing current and saturation characteristic
190: Speed encoder test
195: Measurement q leakage inductance (part 1)
200: Rotating measurement selected
210: Pole position identification selected
220: identification leakage inductance
230: Identification rotor time constant
240: Identification stator inductance
250: Identification stator inductance LQLD
260: Identification circuit
270: Identification stator resistance
290: Identification valve lockout time
300: Stationary measurement selected
Note: For r0047 = 300:
This value is also displayed if encoder calibration p1990 is selected.
Description: Displays the effective Motor Data Set (MDS) and the effective Encoder Data Sets (EDS).
Index: [0] = Motor Data Set MDS effective
[1] = Encoder 1 Encoder Data Set EDS effective
[2] = Encoder 2 Encoder Data Set EDS effective
[3] = Encoder 3 Encoder Data Set EDS effective
Dependency: Refer to: p0186, p0187, p0188, p0189, r0838
Note: Value 99 means the following: No encoder assigned (not configured).
r0047 Motor data identification and speed controller optimization / MotID and n_opt
VECTOR_G Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 300 -
r0049[0...3] Motor data set/encoder data set effective / MDS/EDS effective
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8565
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -