SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
619
2 Parameters
2.2 List of parameters
Description: Sets the frequency limiting of the phase controller output for the line-drive synchronization.
Description: Displays the correction frequency for the line-drive synchronization.
Description: Sets the threshold value of the phase synchronism for the line-drive synchronization.
A prerequisite for synchronism is achieved if the phase difference is lower than the threshold value.
Note: Synchronism is reached (r3819.2 = 1), if the AND logic operation of the results from the phase measurement (p3813)
and voltage measurement (p3815) is fulfilled.
Description: Display and connector output for the voltage difference between the measured target voltage and output voltage of
the gating unit of the closed-loop control for line-drive synchronization.
Description: Sets the threshold value of the voltage difference for the line-drive synchronization.
A prerequisite for synchronism is reached if the voltage difference is less than the threshold value.
p3811[0...n] Sync-line-drive frequency limiting / Sync f_lim
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 1.00 [Hz] 0.20 [Hz]
r3812 CO: Sync-line-drive correction frequency / Sync f_corr
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3080, 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
p3813[0...n] Sync-line-drive phase synchronism threshold value / Sync Ph_sync thrsh
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1.00 [°] 20.00 [°] 2.00 [°]
r3814 CO: Sync-line-drive voltage difference / Sync U_diff
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p3815[0...n] Sync-line-drive voltage difference threshold value / Sync U_diff thresh
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 10.00 [%]