SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
559
2 Parameters
2.2 List of parameters
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the delay time to evaluate the load monitoring.
Description: Sets the torque threshold value for the message "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: r0033, p2195, r2199
Description: Sets the switch-off delay time for the negated signal "run-up completed".
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency: Refer to: p2174, p2194
p2190[0...n] Load monitoring torque threshold 3 lower / M_thresh 3 lower
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2192[0...n] Load monitoring delay time / Load monit t_del
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 65.00 [s] 10.00 [s]
p2194[0...n] Torque threshold value 2 / M_thresh val 2
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 90.00 [%]
p2195[0...n] Torque utilization switch-off delay / M_util t_off
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000.0 [ms] 800.0 [ms]