3 Function diagrams
3.27 Terminal Module 150 (TM150)
Fig. 3-219 9625 – Temperature evaluation structure (channels 0 ... 11)
- 9625 -
Function diagram
87654321
fp_9625_51_eng.vsd
SINAMICS
04.12.12 V04.08.00
Terminal Module 150 (TM150) - Temperature evaluation structure (channels 0  11)
DO: TM150
X53x.3
X53x.4
3 wire
X53x.2
X53x.1 X53x.1
X53x.2
4 wire
X53x.3
X53x.4
-
+
1x2 wire 2x2 wire
X53x.1
X53x.2
-
+
X53x.3
X53x.4
X53x.1
X53x.2
0.83 mA
-
+
-
+
-
+
-
+
Channel 0
Channel 6 (only for 2x2 wire)
X531
X532
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
p4108[0]
p4108[1]
X533
p4108[2]
X534
p4108[3]
X535
p4108[4]
X536
p4108[5]
Channel 1
Channel 7 (only for 2x2 wire)
Channel 2
Channel 8 (only for 2x2 wire)
Channel 3
Channel 9 (only for 2x2 wire)
Channel 4
Channel 10 (only for 2x2 wire)
Channel 5
Channel 11 (only for 2x2 wire)
p4111[0].0
...
Group 0
...
p4111[0].11
Channel 0
Channel 11
p4111[1].0
...
Group 1
...
p4111[1].11
p4111[2].0
...
Group 2
...
p4111[2].11
r4114[0]
Mean value
r4113[0]
Minimum value
r4112[0]
Maximum value
r4114[2]
Mean value
r4113[2]
Minimum value
r4112[2]
Maximum value
r4114[1]
Mean value
r4113[1]
Minimum value
r4112[1]
Maximum value
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
Calculation and
Evaluation
Mot_temp S_src
(0)
p0603
Mot_temp S_src 2
(0)
p0608[0...3]
Mot_temp S_src 3
(0)
p0609[0...3]
IF1 PZD send word
(0)
p2051[x]
Channel 0
[9626]
[9627]
X53x.3
X53x.4
<1>
<1> x = 1, 2, 3, 4, 5, 6
<2> Connect measuring cables.
<3> Carefully read the safety notes included in the parameter description for p4111!
<1> <1> <1>
Sensor resistance
r4101[0]
A35211
Channel 0 alarm is present
r4104.0
F35207
Channel 0 fault is present
r4104.1
r4105[0]
Temperature actual value
<2> <2>
-
+
Channel 5
Channel 6  11
0.83 mA
0.83 mA0.83 mA 0.83 mA
Sensor type
p4100[0]
<3>
Sensor error effect
p4117[0...2] (0)