2 Parameters
2.2 List of parameters
SINAMICS G130/G150
682 List Manual (LH2), 07/2016, A5E03263479A
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm & timer
60: PT1000
Dependency: Refer to: r0458, p0600, p0601
Note: This parameter is effective only when p0601 = 10.
PTC thermistor: Tripping resistance = 1650 Ohm
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
Description: Sets the sensor type of the second temperature sensor for the motor temperature monitoring.
Value: 0: No sensor
10: PTC fault
11: PTC alarm
12: PTC alarm & timer
20: KTY84
30: Bimetallic NC contact fault
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm & timer
60: PT1000
Dependency: Refer to: r0458, p0600, p0601
Note: This parameter is effective only when p0601 = 10.
Terminals for KTY84/PT1000: X200.1, X200.2
PTC thermistor: Tripping resistance = 1650 Ohm
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
Description: Sets the sensor type of the third temperature sensor for the motor temperature monitoring.
Value: 0: No sensor
10: PTC fault
11: PTC alarm
12: PTC alarm & timer
20: KTY84
30: Bimetallic NC contact fault
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm & timer
60: PT1000
Dependency: Refer to: r0458, p0600, p0601
Note: This parameter is effective only when p0601 = 10.
Terminals for PTC triplet and bimetallic: X200.3, X200.4
PTC thermistor: Tripping resistance = 1650 Ohm
p4601[0...n] Motor temperature sensor 2 sensor type / Temp_sens 2 type
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: EDS, p0140 Func. diagram: 8016
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 60 0
p4602[0...n] Motor temperature sensor 3 sensor type / Temp_sens 3 type
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: EDS, p0140 Func. diagram: 8016
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 60 0