2 Parameters
2.2 List of parameters
SINAMICS G130/G150
970 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the time remaining before dynamization and testing of the safety switch-off signal paths (forced checking
procedure).
Dependency: Refer to: A01699
Description: Save the safety parameters for the basic functions on the Motor Module/Hydraulic Module.
Note: The parameter values are saved in the following indices:
p9801: index 20...23
p9802: index 28...31
p9810: index 36...39
p9811: index 116...119
p9812: indices 148...151
p9821: index 84...87
p9822[0]: index 92...95
p9822[1]: index 100...103
p9825[0]: index 124...127
p9825[1]: index 132...135
p9826: index 140...143
p9850: index 44...47
p9851: index 76...79
p9852: index 52...55
p9858: index 60...63
p9897: index 108...111
p9899: index 68...71
Depending on the existing technology, configuration and firmware version, it is possible that not all of the listed
parameters are available.
Description: CRC via Node Identifier of the Control Unit.
Note: CU: Control Unit
r9660 SI forced checking procedure remaining time / SI FCP remain
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [h] - [h] - [h]
p9665[0...255] SI Motor Module parameter save / SI MM par save
VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex 00FF hex 0000 hex
p9670 SI module identification Control Unit / Module ID CU
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP,
VECTOR_G
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4294967295 0