2 Parameters
2.2 List of parameters
SINAMICS G130/G150
628 List Manual (LH2), 07/2016, A5E03263479A
Dependency: Refer to: p3829, p3845
Description: Sets the number of Braking Modules connected in parallel in a DC link.
Note: The parameter can only be written to if the infeed is in the commissioning mode (p0010 = 2).
Description: Signal to energize terminal X21.1 "inhibit/acknowledgment" on the Braking Module.
This binector output is used as signal source to interconnect to a digital output.
For "booksize" formats the digital output must be connected to terminal X21.1 and for "chassis" formats the digital
output must be connected to terminal X21.3 of the particular Braking Module.
Warning: Check that binector outputs BO: r3861.n are connected correctly and that the appropriate digital outputs are wired
correctly.
If the interconnection/wiring is incorrect, the software could execute a different (incorrect) function via binector
outputs BO: r3861.n if the Braking Module develops a fault.
Description: Sets the delay time for switching in the DC link fast discharge.
Dependency: Refer to: p3863, r3864
Note: The DC link fast discharge is only possible for "booksize" formats. This function is not supported for "chassis"
formats.
p3860 Number of Braking Modules connected in parallel / BM qty par_cct
B_INF (Brk Mod ext) Can be changed: C2(2) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: 9951
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 8 1
r3861.0...7 BO: Braking Module inhibit/acknowledgment / BM inhib/ackn
B_INF (Brk Mod ext) Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 9951
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Inhibit/acknowledge Braking Module 1 High Low -
01 Inhibit/acknowledge Braking Module 2 High Low -
02 Inhibit/acknowledge Braking Module 3 High Low -
03 Inhibit/acknowledge Braking Module 4 High Low -
04 Inhibit/acknowledge Braking Module 5 High Low -
05 Inhibit/acknowledge Braking Module 6 High Low -
06 Inhibit/acknowledge Braking Module 7 High Low -
07 Inhibit/acknowledge Braking Module 8 High Low -
p3862 Braking Module DC link fast discharge delay time / BM DC-dischg t_del
B_INF (Brk Mod ext) Can be changed: C1(3), T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 9951
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
500 [ms] 4294967295 [ms] 1000 [ms]