EasyManua.ls Logo

Siemens G130 - Fig. 3-191 8726 - Status word, sequence control infeed

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Function diagrams
3.22 Basic Infeed
SINAMICS G130/G150
1314 List Manual (LH2), 07/2016, A5E03263479A
Fig. 3-191 8726 – Status word, sequence control infeed
- 8726 -
Function diagram
87654321
fp_8726_54_eng.vsd
DO: B_INF
S120/S150/G130/G150
19.06.15 V04.08.00
Basic Infeed - Status word, sequence control, infeed
[8732] From sequencer
[8732] From sequencer
[8732] From sequencer
[8732] From sequencer
[8732] From sequencer
[8750] From power unit
[8738.4] From line contactor control
p0115[3] (2000.00 μs)
r0899.0
r0899.1
r0899.2
r0899.4
r0899.6
r0899.11
r0899.12
r0899.9
r0899
ZSW sequence ctrl
<1> The drive object is ready to accept data.
<2> Only for S120 and G150.
Bit 9 = 1 --> Ready to exchange process data
1 = Ready for operation
1 = Ready for switching on
Status word sequence control infeed
1 = Operation enabled
Reserved
1 = No OFF2 active
1 = Switching on inhibited
Reserved
Reserved
1 = Control requested
Reserved
1 = Precharging completed
1 = Line contactor closed
Reserved
Reserved
Reserved
Reserved
<1>
[8760.5]
<2>
Bit No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Table of Contents