SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
597
2 Parameters
2.2 List of parameters
Description: Sets the suppression of r2139.3 "Fault present" for certain fault responses.
Dependency: Refer to: p0491, r2139
Note: Depending on the suppression of a fault reaction in this parameter, r2139.1 "Acknowledgment required" is set when
at least one fault occurs.
For bit 08:
The suppression is only effective if p0491 = 1.
Description: Sets the threshold value for the "excitation current outside tolerance" message for the excitation current monitoring.
If the absolute value of the difference between the excitation current setpoint and actual value (r1641 - r1626)
exceeds the threshold value and the hysteresis is longer than the selected delay time, then fault F07913 is output.
This fault is withdrawn when the threshold voltage is undershot.
Dependency: Refer to: r1626, r1641, p3202, p3203
Refer to: F07913
Note: The monitoring function is only carried out for separately excited synchronized motors (p0300 = 5).
Description: Sets the hysteresis for the "excitation current outside tolerance" message for the excitation current monitoring.
Dependency: Refer to: p3201, p3203
Refer to: F07913
Note: The monitoring function is only carried out for separately excited synchronized motors (p0300 = 5).
p3135 Suppress active fault / Supp act flt
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: 8060
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 Suppression of fault response ENCODER ON OFF -
10 Suppression of fault response NONE ON OFF -
p3201[0...n] Excitation current outside the tolerance threshold value / I_exc n Tol thresh
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.1 [%] 100.0 [%] 10.0 [%]
p3202[0...n] Excitation current outside the tolerance hysteresis / I_exc n Tol hyst
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.1 [%] 100.0 [%] 10.0 [%]