EasyManua.ls Logo

Siemens G130 - r7229[0...n] CO: Par_circuit phase current actual value sum U, V, W; I_phase sum UVW; r7230[0...n] CO: Par_circuit DC link voltage actual value; Vdc_act; r7231[0...n] CO: Par_circuit phase voltage actual value phase U; U_phase U act val; r7232[0...n] CO: Par_circuit phase voltage actual value phase V; U_phase V act val

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
765
2 Parameters
2.2 List of parameters
Description: Display and connector output for the measured sum of the currents in phases U, V and W as instantaneous value.
The summed value of all power units is displayed in r0069[6].
Description: Displays the measured actual value of the DC link voltage.
The average value of all power units is displayed in r0070.
Description: Displays the actual voltage, phase U.
The average value of all power units is displayed in r0089[0].
Description: Displays the actual voltage, phase V.
The average value of all power units is displayed in r0089[1].
Description: Displays the actual voltage, phase W.
The average value of all power units is displayed in r0089[2].
r7229[0...n] CO: Par_circuit phase current actual value sum U, V, W / I_phase sum UVW
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Unit group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7230[0...n] CO: Par_circuit DC link voltage actual value / Vdc_act
VECTOR_G (Parallel),
B_INF (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Unit group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r7231[0...n] CO: Par_circuit phase voltage actual value phase U / U_phase U act val
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Unit group: 5_3 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r7232[0...n] CO: Par_circuit phase voltage actual value phase V / U_phase V act val
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Unit group: 5_3 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r7233[0...n] CO: Par_circuit phase voltage actual value phase W / U_phase W act val
VECTOR_G (Parallel) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Unit group: 5_3 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]

Table of Contents

Related product manuals