2 Parameters
2.2 List of parameters
SINAMICS G130/G150
94 List Manual (LH2), 07/2016, A5E03263479A
Description: Configuration of the motor when commissioning the motor.
Dependency: For standard induction motors (p0301 > 10000), bit 0 is automatically pre-assigned the connection type of the
selected data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
Refer to: p0304, p0305
Note: For bit 00:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically
converted to the selected connection type (star/delta).
For instance, this can be necessary if an 1LE1 motor is selected using the Article number (MLFB) or code number
(p0300 = 100, p0301 = 1x0xx), and the motor connection type does not correspond to that of the data set.
Description: Copying a Motor Data Set (MDS) into another.
Index: [0] = Source motor data set
[1] = Target motor data set
[2] = Start copying procedure
Note: Procedure:
1. In Index 0, enter which motor data set should be copied.
2. In Index 1, enter the motor data set data that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0139[2] is automatically set to 0 when copying is completed.
When copying, p0131 is not taken into account.
Description: Sets the number of Encoder Data Sets (EDS).
Note: When parameterizing the drive with "no encoder" there must be at least one encoder data set (p0140 >= 1).
p0133[0...n] Motor configuration / Motor config
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: PMSM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor connection type Delta Star -
p0139[0...2] Copy Motor Data Set MDS / Copy MDS
VECTOR_G Can be changed: C2(15) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8575
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 31 0
p0140 Number of Encoder Data Sets (EDS) / EDS count
VECTOR_G Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8570
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 16 1