SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1939
4 Faults and alarms
4.2 List of faults and alarms
Note:
For all alarm values, the following applies: currently set configuration has not been activated.
DHCP: Dynamic Host Configuration Protocol
See also: p8940 (CBE2x Name of Station), p8941 (CBE2x IP address), p8942 (CBE2x Default Gateway), p8943
(CBE2x Subnet Mask), p8944 (CBE2x DHCP Mode)
Remedy: - check the required interface configuration (p8940 and following), correct if necessary, and activate (p8945).
or
- reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
See also: p8945 (CBE2x interface configuration)
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50011 (F) EtherNetIP/COMM BOARD: configuration error
Message value: %1
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: CBE20 EtherNet/IP:
An EtherNet/IP controller attempts to establish a connection using an incorrect configuring telegram.
The telegram length set in the controller does not match the parameterization in the drive device.
Remedy: Check the set telegram length.
For p0922 not equal to 999, then the length of the selected telegram applies.
For p0922 = 999, the maximum interconnected PZD (r2067) applies.
See also: p0922, r2067, r8867
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50020 (F) PNCOMM BOARD: Second controller missing
Message value: -
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: CBE20:
The PROFINET function "Shared Device" has been activated (p8829 = 2). However, only the connection to a
PROFINET controller is present.
See also: p8829 (CBE2x remote controller number)
Remedy: CBE20:
Check the configuration of the PROFINET controllers as well as the p8829 setting.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY