4 Faults and alarms
4.2 List of faults and alarms
A49204 (N) Excitation switch-off alarm
Message value: -
Message class: Hardware/software error (1)
Drive object: VECTOR_G
Component: Control Unit (CU) Propagation: GLOBAL
Reaction: NONE
Acknowledge: NONE
Cause: When switching off the excitation, after the delay time (p1647) has expired, the excitation current has still not
decayed to zero.
Remedy: Extend the switch-off delay time in (p1647).
Note:
The alarm is automatically reset after adapting p1647.
See also: p1647 (Excitation switch-off delay time)
Reaction upon N: NONE
Acknowl. upon N: NONE
A49998 Recorder trigger event occurred
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, VECTOR_G
Component: None Propagation: GLOBAL
Reaction: NONE
Acknowledge: NONE
Cause: A recorder trigger event has occurred. The data are then written to the memory card, specifying the event number.
Alarm value (r2124, interpret decimal):
Event number.
Remedy: Not necessary.
This message disappears automatically.
A50001 (F) PN/COMM BOARD: Configuration error
Message value: %1
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: CBE20:
A PROFINET controller attempts to establish a connection using an incorrect configuring telegram. The "Shared
Device" function has been activated (p8829 = 2).
Alarm value (r2124, interpret decimal):
10: A CPU sends a PROFIsafe telegram.
11: F CPU sends a PZD telegram.
12: F CPU without an A CPU.
13: F CPU with more PROFIsafe subslots than activated with p9601.3.
14: F CPU with fewer PROFIsafe subslots than activated with p9601.3.
15: PROFIsafe telegram of the F-CPU does not match the setting in p60022.
See also: p8829 (CBE2x remote controller number), p9601 (SI enable functions integrated in the drive (Control Unit))
Remedy: CBE20:
Check the configuration of the PROFINET controllers as well as the p8829 and p9601.3 setting.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY