2 Parameters
2.2 List of parameters
SINAMICS G130/G150
148 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the rotor/secondary section leakage inductance of the motor.
For separately excited synchronous motors: Sets the damping inductance in the rotor direction (d-axis).
This value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910) (not for separately excited synchronous motors).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
VECTOR:
If the rotor leakage inductance (p0358) for induction motors is changed outside the commissioning phase (p0010 >
0), then the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then advised
to repeat the measurement for the saturation characteristic (p1960).
Description: Sets the damping inductance of the separately excited synchronous motor quadrature to the rotor direction (q axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2).
Description: Sets the magnetizing inductance of the motor.
For separately excited synchronous motors: Sets the saturated magnetizing inductance in the rotor direction (d-axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor
identification routine (p1910) (not for separately excited synchronous motors).
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
p0358[0...n] Motor rotor leakage inductance / damping inductance d axis / Mot L_r leak / LDd
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: 15_1 Unit selection: p0349
Not for motor type: PMSM, REL, RESM Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0359[0...n] Motor damping inductance q axis / Mot L_damp q
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: 15_1 Unit selection: p0349
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0360[0...n] Motor magnetizing inductance/magn. inductance d axis saturated / Mot Lh/Lh d sat
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: 15_1 Unit selection: p0349
Not for motor type: PMSM, REL, RESM Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 10000.00000 [mH] 0.00000 [mH]