2 Parameters
2.2 List of parameters
SINAMICS G130/G150
1068 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the telegram for the safety information channel (SIC) / safety control channel (SCC).
The SIC/SCC telegram p60122 is attached directly to the PZD telegram p0922/p2079.
Value: 700: Supplementary telegram 700, PZD-0/3
701: Supplementary telegram 701, PZD-2/5
999: Free telegram configuration with BICO
Note: The clearance to the PZD telegram can be increased using p2070/p2071.
After changing p0922/p2079 or p2070/p2071, then p60122 must be set again.
The telegram interconnections can only be changed if p60122 and p0922 are both set to 999.
Description: Displays PROFINET Name of Station.
Notice: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
Description: Displays PROFINET IP of Station.
p60122 IF1 PROFIdrive SIC/SCC telegram selection / IF1 SIC/SCC telegr
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 2423
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
700 999 999
r61000[0...239] PROFINET Name of Station / PN Name of Station
CU_G130_PN,
CU_G150_PN,
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: 2410
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r61001[0...3] PROFINET IP of Station / PN IP of Station
CU_G130_PN,
CU_G150_PN,
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: 2410
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -