SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
69
2 Parameters
2.2 List of parameters
Description: Displays the torque utilization as a percentage.
The torque utilization is obtained from the required smoothed torque referred to the torque limit.
Dependency: Refer to: r0033
Note: The torque utilization is available smoothed (r0033) and unsmoothed (r0081).
The torque utilization is obtained from the required torque referred to the torque limit as follows:
- Positive torque: r0081 = (r0079 / r1538) * 100 %
- Negative torque: r0081 = (-r0079 / -r1539) * 100 %
Description: Displays the instantaneous active power.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency: Refer to: r0032
Note: The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
Description: Displays the instantaneous active power.
Dependency: Refer to: r0032
Notice: For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note: The active power is available smoothed (r0032) and unsmoothed (r0082).
Description: Displays the flux setpoint.
r0081 CO: Torque utilization / M_Utilization
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8012
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r0082[0...2] CO: Active power actual value / P_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6714, 6799
P-Group: Displays, signals Unit group: 14_5 Unit selection: p0505
Not for motor type: - Scaling: r2004 Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]
r0082 CO: Active power actual value / P_act
B_INF Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8750, 8850,
8950
P-Group: Displays, signals Unit group: 14_7 Unit selection: p0505
Not for motor type: - Scaling: r2004 Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]
r0083 CO: Flux setpoint / Flex setp
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]