2 Parameters
2.2 List of parameters
SINAMICS G130/G150
332 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the signal source for speed setpoint 2 of the speed controller.
Dependency: Refer to: p1155, r1170
Note: For OFF1/OFF3, the ramp-function generator ramp is effective.
The ramp-function generator is set (SERVO: to the actual value, VECTOR: To the setpoint (r1170)) and stops the
drive corresponding to the ramp-downtime (p1121 or p1135). While stopping via the ramp-function generator,
STW1.4 is effective (enable ramp-function generator).
When the function module "position control" (r0108.3 = 1) is activated, this connector input is interconnected as
follows as standard:
CI: p1160 = r2562
Description: Displays the speed setpoint after the addition of the speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency: Refer to: p1155, p1160
Note: The value is only correctly displayed at r0899.2 = 1 (operation enabled).
Description: Display and connector output for the speed setpoint after selecting the ramp-function generator.
The value is the sum of speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency: Refer to: r1150, p1155, p1160
Description: Sets the configuration for the speed setpoint.
p1160[0...n] CI: Speed controller speed setpoint 2 / n_ctrl n_set 2
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3001, 3080
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0
r1169 CO: Speed controller speed setpoints 1 and 2 / n_ctrl n_set 1/2
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3080
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1170 CO: Speed controller setpoint sum / n_ctrl setp sum
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3001, 3080,
6300
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1189[0...n] Speed setpoint configuration / n_ctrl config
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: DDS, p0180 Func. diagram: 3080
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0011 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Interpolation ramp-fct gen/speed controller
active
Yes No 3080
01 Interpol. op-loop ctrl /speed controller active Yes No 3080