2 Parameters
2.2 List of parameters
SINAMICS G130/G150
644 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the signal source for the digital output DO 1 (X542.4, X542.5, X542.6) of Terminal Module 31 (TM31).
Digital output 1 of TM31 is a relay output.
If the signal at the binector input p4031 is low, then terminal COM 1 (X542.5) is connected to NC 1 (X542.4). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4031 is high, then terminal COM 1 (X542.5) is connected to NO 1 (X542.6).
Note: DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
Description: Sets the signal source for terminal DO 1 (X481.6) of the Terminal Board 30 (TB30).
Note: DO: Digital Output
Description: Sets the signal source for terminal DO 2 (X481.7) of the Terminal Board 30 (TB30).
Note: DO: Digital Output
Description: Sets the signal source for terminal DO 3 (X481.8) of the Terminal Board 30 (TB30).
Note: DO: Digital Output
p4031 BI: TM31 signal source for terminal DO 1 / TM31 s_src DO 1
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9549, 9556
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4031 BI: TB30 signal source for terminal DO 1 / TB30 s_src DO 1
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9102
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4032 BI: TB30 signal source for terminal DO 2 / TB30 s_src DO 2
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9102
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p4033 BI: TB30 signal source for terminal DO 3 / TB30 s_src DO 3
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9099, 9102
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0