2 Parameters
2.2 List of parameters
Description: Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
BI: p0852 = 0 signal
Inhibit operation (suppress pulses).
BI: p0852 = 1 signal
Enable operation (pulses can be enabled).
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the command "control by PLC/no control by PLC".
For the PROFIdrive profile, this command corresponds to control word 1 bit 10 (STW1.10).
BI: p0854 = 0 signal
No control by PLC
BI: p0854 = 1 signal
Master control by PLC.
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then binector input p0854 should be set to 1.
If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies
regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
Description: Sets the signal source for the command "control by PLC/no control by PLC".
For the PROFIdrive profile, this command corresponds to control word 1 bit 10 (STW1.10).
BI: p0854 = 0 signal
No control by PLC
p0852[0...n] BI: Enable operation/inhibit operation / Enable operation
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2501, 8820,
8920
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p0854[0...n] BI: Control by PLC/no control by PLC / Master ctrl by PLC
VECTOR_G, B_INF Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2501, 8720,
8820, 8920
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p0854 BI: Control by PLC/no control by PLC / Master ctrl by PLC
ENC Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2501, 8720,
8820, 8920
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1