2 Parameters
2.2 List of parameters
SINAMICS G130/G150
132 List Manual (LH2), 07/2016, A5E03263479A
Dependency: Refer to: p0145, p0300
Note: SMI: SINAMICS Sensor Module Integrated
Description: Sets the rated motor voltage (rating plate).
Dependency: Refer to: p0349
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Description: Sets the rated motor current (rating plate).
Dependency: Refer to: p0349
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0305 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly. This is not the case when commissioning the motor (p0010 = 3).
If the rated motor current exceeds twice the maximum drive converter current (r0209), then the maximum current is
reduced due to the current harmonics that increase overproportionally (r0067).
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Description: Number of motors that can be operated in parallel using one motor data set.
Depending on the motor number entered, internally an equivalent motor is calculated.
The following should be carefully observed for motors connected in series:
The following rating plate data should only be entered for one motor:
- resistances and inductances: p0350 ... p0361
- currents: p0305, p0320, p0323, p0325, p0329, p0389, p0390, p0391, p0392
- power ratings: p0307
- masses/moments of inertia: p0341, p0344
All other parameters take into account the replacement/equivalent motor (e.g. r0331, r0333).
Recommendation: For motors connected in parallel, external thermal protection should be provided for each individual motor.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor data set selected MDS1 MDS0 -
01 Motor connection type Delta Star -
02 Windings can be changed Yes No -
03 Windings can be changed number 2 0 -
p0304[0...n] Rated motor voltage / Mot U_rated
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6301, 6724
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [Vrms] 20000 [Vrms] 0 [Vrms]
p0305[0...n] Rated motor current / Mot I_rated
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6301
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0306[0...n] Number of motors connected in parallel / Motor qty
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Unsigned8 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: SESM, RESM Scaling: - Expert list: 1
Min Max Factory setting
1 50 1