EasyManua.ls Logo

Siemens G130 - F05056 Parallel circuit: Power unit EEPROM versions differ; F05057 Parallel circuit: Power unit firmware versions differ; F05058 Parallel circuit: VSM EEPROM versions differ

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1523
4 Faults and alarms
4.2 List of faults and alarms
Fault value (r0949, interpret decimal):
Parameter in which the inadmissible power unit code number was detected.
Remedy: - Use power units with the same code number.
For booksize drive units, the following additionally applies:
- use power units which are permitted for a parallel connection.
- reduce the number of power units being used in the parallel connection.
F05056 Parallel circuit: Power unit EEPROM versions differ
Message value: Parameter: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: GLOBAL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: The EEPROM versions of the power units do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy: Use power units with the same EEPROM version.
Note:
For parallel circuit configurations, only power units with identical EEPROM versions may be used.
F05057 Parallel circuit: Power unit firmware versions differ
Message value: Parameter: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: GLOBAL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: The firmware versions of the power units connected in parallel do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy: Use power units with the same firmware version.
For parallel circuit configurations, only power units with identical firmware versions may be used.
F05058 Parallel circuit: VSM EEPROM versions differ
Message value: Parameter: %1
Message class: General drive fault (19)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The EEPROM versions of the Voltage Sensing Modules (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy: For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical EEPROM versions may be
used.