SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
229
2 Parameters
2.2 List of parameters
Description: Setting to inhibit the calculation of reference parameters (e.g. p2000) when automatically calculating the motor and
closed-loop control parameters (p0340, p3900).
Value: 0: No
1: Yes
Notice: The inhibit for the reference value calculation is canceled when new motor parameters (e.g. p0305) are entered and
only one drive data set exists (p0180 = 1). This is the case during initial commissioning.
Once the motor and control parameters have been calculated (p0340, p3900), the inhibit for the reference value
calculation is automatically re-activated.
Note: If value = 0:
The automatic calculation (p0340, p3900) overwrites the reference parameters.
If value = 1:
The automatic calculation (p0340, p3900) does not overwrite the reference parameters.
Description: This parameter is used to calculate all parameters that depend on the technology of the application (p0500).
All of the parameters are calculated that can also be determined using p0340 = 5.
Value: 0: No calculation
1: Complete calculation
Note: At the end of the calculations, p0578 is automatically set to 0.
Description: Selects the units for the parameters of the technology controller.
For p0595 = 1, 2, the reference quantity set in p0596 is not active.
Value: 1: %
2: 1 referred no dimensions
3: bar
4: °C
5: Pa
6: ltr/s
7: m³/s
8: ltr/min
9: m³/min
10: ltr/h
11: m³/h
12: kg/s
13: kg/min
p0573 Inhibit automatic reference value calculation / Inhibit calc
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Applications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0578[0...n] Calculate technology-dependent parameters / Calc tec par
VECTOR_G Can be changed: C2(5), T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Applications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0595 Technological unit selection / Tech unit select
VECTOR_G
(Tech_ctrl)
Can be changed: C2(5) Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Applications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 32 1