2 Parameters
2.2 List of parameters
Description: Sets the sensor type of the fourth temperature sensor for the motor temperature monitoring.
Value: 0: No sensor
10: PTC fault
11: PTC alarm
12: PTC alarm & timer
20: KTY84, PT100, PT1000
30: Bimetallic NC contact fault
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm & timer
Dependency: Refer to: r0458, p0600, p0601
Note: This parameter is effective only when p0601 = 11.
PTC thermistor: Tripping resistance = 1650 Ohm
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
Description: Displays the actual temperature in the motor measured through temperature channels 1 ... 4.
Index: [0] = Temperature channel 1
[1] = Temperature channel 2
[2] = Temperature channel 3
[3] = Temperature channel 4
Note: For a value not equal to -200.0 °C, the following applies:
- this temperature display is valid.
- a KTY/PT1000 temperature sensor is connected.
For a value equal to -200.0 °C, the following applies:
- this temperature display is not valid (temperature sensor error).
- a PTC sensor or bimetallic NC contact is connected.
- the temperature sensor evaluation is deactivated (p0600 = 0 or p0601 = 0).
- the sensor channel is deactivated (p460x = 0 or p461x = 0).
Description: Displays the encoder diagnostics for the PROFIdrive interface.
p4613[0...n] Motor temperature sensor 4 sensor type MDS / Temp sens4 typ MDS
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 32 10
r4620[0...3] Motor temperature measured / Mot_temp meas
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8016
P-Group: Displays, signals Unit group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r4640[0...95] Encoder diagnostics state machine / Enc diag stat_ma
VECTOR_G, ENC Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -