EasyManua.ls Logo

Siemens G130 - Fig. 3-35 2441 - STW1 control word interconnection (p2038 = 2)

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1141
3 Function diagrams
3.6 PROFIdrive
Fig. 3-35 2441 – STW1 control word interconnection (p2038 = 2)
- 2441 -
Function diagram
87654321
fp_2441_54_eng.vsd
DO: VECTOR
S120/S150/G130/G150
27.06.13 V04.08.00
PROFIdrive - STW1 control word interconnection (p2038 = 2)
<1> Used in telegram 20.
<2> STW1.10 must be set to ensure that the drive object accepts the process data (PZD).
<3> OC = Operating condition.
<4> Interconnection is not disabled.
PROFIdrive sampling time
STW1.0
STW1.1
STW1.2
STW1.3
STW1.4
STW1.5
STW1.6
STW1.8
STW1.9
STW1.11
STW1.12
STW1.13
STW1.14
STW1.15
STW1.7
STW1.10
p0848[0] = r2090.2
p0852[0] = r2090.3
p1140[0] = r2090.4
p1141[0] = r2090.5
p1142[0] = r2090.6
p2103[0] = r2090.7
-
-
p0854[0] = r2090.10
p1113[0] = r2090.11
-
-
p0810[0] = 2090.15
p0840[0] = r2090.0
p0844[0] = r2090.1
= ON (pulses can be enabled)
0 = OFF1 (braking with ramp-function generator, then pulse suppression & ready for switching on)
1 = No OFF2 (enable is possible) <3>
0 = OFF2 (immediate pulse suppression and switching on inhibited)
1 = No OFF3 (enable possible) <3>
0 = OFF3 (braking with the OFF3 ramp p1135, then pulse suppression and switching on inhibited)
1 = Enable operation (pulses can be enabled)
0 = Inhibit operation (suppress pulses)
1 = Operating condition (the ramp-function generator can be enabled)
0 = Inhibit ramp-function generator (set the ramp-function generator output to zero)
1 = Enable the ramp-function generator
0 = Stop the ramp-function generator (freeze the ramp-function generator output)
1 = Enable setpoint
0 = Inhibit setpoint (set the ramp-function generator input to zero)
= 1. Acknowledge faults
Reserved
Reserved
1 = Control by PLC
1 = Setpoint inversion
Reserved
1 = Command Data Set selection CDS bit 0
Reserved
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2546.1]
-
-
[2501.3]
[2505.3]
-
-
-
[2501.3]
[2501.3]
Signal targets for STW1 in Interface Mode VIK-NAMUR (p2038 = 2)
[2610]
[2610]
[3060] [3070] [3080]
[3060] [3070]
[3060] [3070] [3080]
[8060]
-
-
[2501]
[3040]
-
-
[8560]
[2610]
[2610]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Signal
Interconnection
parameters
Meaning
[Function diagram]
internal control word
[Function diagram]
signal target
Inverted
<2>
<1>
<4>
1 = Unconditionally open the holding brake p0855[0] = r2090.12 [2501.3] [2701]

Table of Contents

Related product manuals