Siemens G130 - p4058[0...1] TB30 analog inputs characteristic value y1; TB30 AI char y1; p4059[0...1] TM31 analog inputs characteristic value x2; TM31 AI char x2; p4059[0...1] TB30 analog inputs characteristic value x2; TB30 AI char x2

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
651
2 Parameters
2.2 List of parameters
Description: Sets the scaling characteristic for the analog inputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 2nd value pair of the
characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The unit of this parameter (V or mA) depends on the analog input type.
Refer to: r4056, p4056
Notice: This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog inputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V) of the 2nd value pair of the characteristic.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: The parameters for the characteristic do not have a limiting effect.
p4058[0...1] TB30 analog inputs characteristic value y1 / TB30 AI char y1
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 0.00 [%]
p4059[0...1] TM31 analog inputs characteristic value x2 / TM31 AI char x2
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 20.000 10.000
p4059[0...1] TB30 analog inputs characteristic value x2 / TB30 AI char x2
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-11.000 [V] 11.000 [V] 10.000 [V]