2 Parameters
2.2 List of parameters
SINAMICS G130/G150
612 List Manual (LH2), 07/2016, A5E03263479A
Dependency: Refer to: p3665
Refer to: F34207, A34211
Note: If value r3666 exceeds threshold value p3667 or p3668, then alarm A34211 or fault F34207 is output.
For sensor type PTC (p3665 = 1), the following applies:
- below the nominal response temperature, r3666 = -50°C.
- above the nominal response temperature, r3666 = 250 °C.
Description: Sets the alarm threshold for the temperature sensor on the Voltage Sensing Module (VSM).
Prerequisite:
A KTY/PT1000 temperature sensor is connected, and correspondingly p3665 is set = 2, 6.
Dependency: Refer to: p3665
Refer to: A34211
Note: For sensor type KTY (p3665 = 2), values 181 ... 300 °C result in fault F06255.
The monitoring is deactivated for p3667 = 301.
Description: Sets the shutdown threshold for the temperature sensor of the VSM.
Prerequisite:
A KTY/PT1000 temperature sensor is connected, and correspondingly p3665 is set = 2, 6.
Dependency: Refer to: p3665, p3667
Refer to: F35207
Note: For sensor type KTY (p3665 = 2), values 181 ... 300 °C result in fault F06255.
The monitoring is deactivated for p3668 = 301.
Description: Sets the hysteresis for the alarm threshold of the Voltage Sensing Module (VSM).
Dependency: Refer to: p3667
p3667[0...n] VSM overtemperature alarm threshold / VSM T A thresh
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9886
P-Group: - Unit group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
-100.00 [°C] 301.00 [°C] 150.00 [°C]
p3668[0...n] VSM overtemperature shutdown threshold / VSM T F_thresh
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9886
P-Group: - Unit group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
-100.00 [°C] 301.00 [°C] 180.00 [°C]
p3669[0...n] VSM overtemperature hysteresis / VSM T hyst
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9886
P-Group: - Unit group: 21_2 Unit selection: p0505
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
1.00 [K] 50.00 [K] 3.00 [K]