SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1407
4 Faults and alarms
4.2 List of faults and alarms
F01356 Topology: There is a defective DRIVE-CLiQ component
Message value: Fault cause: %1, Component number: %2, Connection number: %3
Message class: Hardware/software error (1)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE (OFF2)
Acknowledge: IMMEDIATELY
Cause: The actual topology indicates at least one defective DRIVE-CLiQ component.
Fault value (r0949, interpret hexadecimal):
zzyyxx hex:
zz = connection number of the component at which the defective component is connected
yy = component number of the component at which the defective component is connected
xx = fault cause
xx = 1: Component at this Control Unit not permissible.
xx = 2: component with communication defect.
Note:
Pulse enable is withdrawn and prevented.
Remedy: Replace the defective component and restart the system.
F01357 Topology: Two Control Units identified on the DRIVE-CLiQ line
Message value: component number: %1, connection number: %2
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE (OFF2)
Acknowledge: IMMEDIATELY
Cause: In the actual topology, 2 Control Units are connected with one another through DRIVE-CLiQ.
As standard, this is not permitted.
It is only permitted if the Technology Extension OALINK has already been installed on both Control Units.
Fault value (r0949, interpret hexadecimal):
yyxx hex:
yy = connection number of the Control Unit at which the second Control Unit is connected
xx = component number of the Control Unit at which the second Control Unit is connected
Note:
Pulse enable is withdrawn and prevented.
Remedy: - remove the DRIVE-CLiQ connection, restart the systems, install OALINK on both Control Units and commission.
- remove the connection to the second Control Unit and restart.
- for the S120M component DRIVE-CLiQ extension, interchange the hybrid cable (IN/OUT).
A01358 Topology: Line termination not available
Message value: CU connection number: %1, component number: %2, connection number: %3
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: At least one line with distributed drives is not terminated. The last participant on the line must be terminated with a
line termination connector.
This therefore ensures the degree of protection of the distributed drives.
Alarm value (r2124, interpret hexadecimal):
zzyyxx hex:
zz = connection number of the distributed drive where there is no terminating connector
yy = component number
xx = CU connection number
Remedy: Install the line terminating connector for the last distributed drive.