Siemens G130 - p1321[0...n] U;f control programmable characteristic voltage 1; Uf char U1; p1322[0...n] U;f control programmable characteristic frequency 2; Uf char f2; p1323[0...n] U;f control programmable characteristic voltage 2; Uf char U2; p1324[0...n] U;f control programmable characteristic frequency 3; Uf char f3

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
375
2 Parameters
2.2 List of parameters
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
Dependency: Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1322, p1323, p1324, p1325, p1326, p1327
Note: Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
Dependency: The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard
characteristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1323, p1324, p1325, p1326, p1327
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
Dependency: Refer to: p1310, p1311, p1320, p1321, p1322, p1324, p1325, p1326, p1327
Description: The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency: The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard
characteristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1325, p1326, p1327
p1321[0...n] U/f control programmable characteristic voltage 1 / Uf char U1
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6301
P-Group: V/f open-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [Vrms] 10000.0 [Vrms] 0.0 [Vrms]
p1322[0...n] U/f control programmable characteristic frequency 2 / Uf char f2
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6301
P-Group: V/f open-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]
p1323[0...n] U/f control programmable characteristic voltage 2 / Uf char U2
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6301
P-Group: V/f open-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [Vrms] 10000.0 [Vrms] 0.0 [Vrms]
p1324[0...n] U/f control programmable characteristic frequency 3 / Uf char f3
VECTOR_G Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6301
P-Group: V/f open-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]