2 Parameters
2.2 List of parameters
SINAMICS G130/G150
58 List Manual (LH2), 07/2016, A5E03263479A
Dependency: Refer to: r0002
Note: The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a "switching-on inhibited".
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 02 = 1 (enable signal missing), if:
- the signal source in p0848 or p0849 is a 0 signal.
Bit 03 = 1 (enable signal missing), if:
- the signal source in p0852 is a 0 signal.
Bit 04 =1 (armature short-circuit active), if:
- the signal source in p1230 has a 1 signal
Bit 05, Bit 06: Being prepared
Bit 08 = 1 (enable signal missing), if:
- safety functions have been enabled and STO is active.
- a safety-relevant signal is present with a STOP A response.
STO enabled via terminals:
- the pulse enable via terminal EP is missing (booksize: X21, chassis: X41), or the signal source in p9620 is for a 0
signal.
STO enabled via PROFIsafe or TM54F:
- STO is selected via PROFIsafe or TM54F.
Bit 09 = 1 (enable signal missing), if:
- the signal source in p0864 is a 0 signal.
Bit 10 = 1 (enable signal missing), if:
- the signal source in p1140 is a 0 signal.
Bit 11 = 1 (enable signal missing) if the speed setpoint is frozen, because:
- the signal source in p1141 is a 0 signal.
- the speed setpoint is entered from jogging and the two signal sources for jogging, bit 0 (p1055) and bit 1 (p1056)
have a 1 signal.
Bit 12 = 1 (enable signal missing), if:
- the signal source in p1142 is a 0 signal.
- When activating the function module "basic positioner" (r0108.4 = 1), the signal source in p1142 is set to a 0 signal.
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enabled if the fault is removed and was acknowledged and the
"switching-on inhibited" withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- commissioning mode is selected (p0009 > 0 or p0010 > 0).
- there is an OFF2 fault response.
- the drive is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 18 = 1 (enable signal missing), if:
- OFF3 has still not been completed or an OFF3 fault response is present.
Bit 19 = 1 (internal pulse enable missing), if:
- synchronization is running between the basic clock cycle, DRIVE-CLiQ clock cycle and application clock cycle.
18 OFF3 enable internal missing Yes No -
19 Pulse enable internal missing Yes No -
20 Armature short-circuit/DC braking internal
enable missing
Yes No -
21 STOP2 enable internal missing Yes No -
25 Function bypass active Yes No -
26 Drive inactive or not operational Yes No -
27 De-magnetizing not completed Yes No -
28 Brake open missing Yes No -
29 Cooling unit ready signal missing Yes No -
30 Speed controller inhibited Yes No -
31 Jog setpoint active Yes No -