PROFINET COMMANDS
SHOW
PROFINET ALARM
show profinet alarm
Overview Use this command to display the status of the alarms that have been activated.
Alarms are declared and a mapping is provided in the GSD file for the device.
A GSD file is a readable XML file. The file contains both general and device-specific
specifications for communication and network configuration. Each of the entries
describes a feature that is supported by a device.
All AlliedWare Plus™ devices that support PROFINET come with a GSD file.
Syntax
show profinet alarm
Mode User Exec
Example To display PROFINET alarms, use the command:
awplus# show profinet alarm
Output Figure 70-3: Example output from show profinet alarm
awplus#show profinet alarmď€
DIAGNOSISď€
Max: 200 itemsď€
Items in use: 3ď€
[ 0] USI: 0x8002 [Last] Channel: 0x0003 Ch.error: 0x0002 Ext.error 0x8000ď€
Add.value 0x0000002F Qualifier 0x00000000ď€
[ 1] USI: 0x8002 Next: 0 Channel: 0x0001 Ch.error: 0x0005 Ext.error 0x8000ď€
Add.value 0x00000024 Qualifier 0x00000000ď€
[ 2] USI: 0x8002 Next: 1 Channel: 0x0002 Ch.error: 0x0002 Ext.error 0x8000ď€
Add.value 0x00000000 Qualifier 0x00000000