List of parameters
Parameters
1-101
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Detects the Sensor Module assigned to this drive and data set.
Note: While p0144 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Sensor Module.
Description: Setting to activate/de-activate a Voltage Sensing Module (VSM).
Values: 0: De-activate component
1: Activate component
2: Component, de-activate and not present
Recommend.: After inserting a component, before activating, first wait for Alarm A01317.
Dependency: Refer to: r0146
Refer to: A01317
Note: For chassis infeeds, it is not possible to activate/de-activate the Voltage Sensing Module (VSM) via p0145. The
VSM can only be activated/de-activated in the group with the appropriate infeed via p0125[0...n].
The activation of a component can be rejected if the component was inserted for the first time.
In this case, it is only possible to activate the component when the pulses for all of the drive objects are inhibited.
Description: Setting to activate/de-activate an encoder interface (Sensor Module).
Values: 0: De-activate component
1: Activate component
2: Component, de-activate and not present
Recommend.: After inserting a component, before activating, first wait for Alarm A01317.
Dependency: Refer to: r0146
Refer to: A01317
Note: The de-activation of an encoder interface corresponds to the"parking encoder" function and has the same effect.
The activation of a component can be rejected if the component was inserted for the first time.
In this case, it is only possible to activate the component when the pulses for all of the drive objects are inhibited.
p0144[0...n] Sensor Module detection via LED / SM detection LED
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0
p0145[0...n] Voltage Sensing Module, activate/de-activate / VSM act/deact
A_INF, S_INF Can be changed: C1(4), T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: p0140 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 1
p0145[0...n] Activate/de-activate encoder interface / Enc_intf act/deact
SERVO, VECTOR Can be changed: C1(4), U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 1