List of faults and alarms
Faults and Alarms
3-1701
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
N33800 (F) Encoder 3: Group signal
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE)
SERVO: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
Acknowledge: NONE
Cause: The motor encoder has detected at least one fault.
Remedy: Evaluates other actual messages.
Reaction upon F: A_INFEED: OFF2 (NONE)
SERVO: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
F33801 (N, A) Encoder 3 DRIVE-CLiQ: Sign-of-life missing
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE)
SERVO: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: DRIVE-CLiQ communications error between the Control Unit and the encoder involved.
Fault value (r0949, interpret hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.
Remedy: - check the electrical cabinet design and cable routing for EMC compliance
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F33802 (N, A) Encoder 3: Time slice overflow
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE)
SERVO: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: Time slice overflow, encoder 3.
Fault value (r0949, interpret decimal):
9: Time slice overflow of the fast (current controller clock cycle) time slice.
10: Time slice overflow of the average time slice.
12: Time slice overflow of the slow time slice.
999: Timeout when waiting for SYNO, e.g. unexpected return to non-cyclic operation.
Remedy: Reduce the current controller frequency.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE