Siemens SINAMICS S Series - p0282 Line supply undervoltage, alarm threshold; V_l_under A thresh; p0283 Line supply undervoltage, shutdown (trip) threshold; V_l_under tr_thrsh; p0284 Line supply frequency exceeded, alarm threshold; f_l_exc A thresh; p0285 Line supply frequency fallen below, alarm threshold; f_l_under A thresh

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-126
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the alarm threshold for a line undervoltage condition.
The setting is made as a percentage of the drive unit supply voltage (p0210).
Dependency: Refer to: p0222, p0224, p0225, p0226, p3421, p3422
Refer to: A06105
Note: If synchronizing voltages are not detected, the line supply voltage is estimated using a model. It is therefore impor-
tant to ensure that drive unit data is correctly specified.
Description: Sets the trip threshold for the line supply undervoltage.
The setting is made as a percentage of the drive unit supply voltage (p0210).
Dependency: Refer to: p0282
Refer to: F06100
Notice: For Active Line Modules booksize, the following applies:
When operated without Active Interface Module (p0220 = 41 ... 45), the minimum shutdown threshold is 75 %.
Description: Sets the alarm threshold for an excessively high line frequency.
Dependency: Set as a percentage of the rated line frequency.
Refer to: p0211
Description: Sets the alarm threshold for an excessively low line frequency.
Dependency: Set as a percentage of the rated line frequency.
Refer to: p0211
p0282 Line supply undervoltage, alarm threshold / V_l_under A thresh
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8860, 8960
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
10 [%] 100 [%] 85 [%]
p0283 Line supply undervoltage, shutdown (trip) threshold / V_l_under tr_thrsh
A_INF, S_INF Can be changed: C2(1), T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8860, 8960
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
10 [%] 100 [%] 75 [%]
p0284 Line supply frequency exceeded, alarm threshold / f_l_exc A thresh
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8864, 8964
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
100.0 [%] 300.0 [%] 110.0 [%]
p0285 Line supply frequency fallen below, alarm threshold / f_l_under A thresh
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8864, 8964
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 90.0 [%]